Answer: (1) The motor should be started separately to check whether the direction of rotation is correct.
(2) After the motor is connected to the compressor, it should be rotated several times and should be flexible without blocking.
(3) The compressor should be started for 2~3 minutes. After confirming that there are no abnormalities, it should be operated continuously for at least 30 minutes.
(4) The vibration and bearing temperature of the continuously running air compressor should be normal, the bearing temperature should not exceed , the body temperature should not exceed , and the vibration intensity should not exceed 7.1mm/s.
(5) The oil level mirror should be clear, the oil level line mark should be clear, the oil level should be normal, the oil quality should be good, and there should be no oil leakage or oil throwing at the bearing.
(6) After the machine is tested, make a detailed record of the test run and the problems found during the inspection.