Answer: (1) Reasonably design the suction and exhaust pipes to reduce pressure loss and leakage in the pipes.
(2) Use variable frequency speed regulation to achieve capacity adjustment. Compared with the ordinary air intake throttling type, the energy saving effect of variable frequency air compressors can reach 30%~40%.
(3) Use direct-connected motor drive to reduce mechanical transmission loss, and use efficient permanent magnet synchronous motors.
(4) Use microcomputer control to reduce the range of loading and unloading, and reduce the exhaust pressure setting while ensuring the minimum pressure of the gas-using equipment.
(5) Multi-unit control automatically selects the number of necessary machines according to the actual air usage, thereby avoiding the huge waste caused by unnecessary simultaneous operation of multiple machines.